It’s not everyday you get to buy a new AC unit, I though it would be a good idea to finally take some thermal images of the coils that do all the work in a heat exchanger.

🔵 condenser unit (outdoor), placed near window

📋 Data Sheet ( as per manufacturer ).

  • GREE GSH-12PUV410, 1 Ton.

  • Inverter.

  • 12000 BTU.

  • Hot + Cold.

  • Refrigerant Type - R22

  • Operating current : 6.0 Amp

  • Power Consumption : 1250 Watt.

Since I had a amp meter, I did a site reading of the operating currrent. My main’s voltage was 218V, while my amp meter was showing Amin ~ 2.1 and Amax ~ 6.2 Amp.

So it seems my AC unit was consuming ~ 460 Watts while operating at it’s low setting, and 1,351 Watt at full capacity.

Now time to take some thermal images …

🔵 outdoor unit / thermal image ( distant )

🔵 close up of colder coil in unit, temperature difference of ~10°C between coil.

🔵 using red, outdoor temperature is 30°C, hottest coil is at 46°C. ( 16°C differential ).

The images was taken after 2 hours of operation, to give the AC time to fully pass on the gasses into all the coils, it was quite peculiar to see two coils being ~ 6 degree colder than the others, was there some sort of blockage, preventing the gas from reaching ?

I did not expect there to be cold coils in the condenser unit at all, especially since it’s a brand new unit !

I had so many questions, is it normal for condenser coils to have thermal gaps ? especially new units ?